Residual Current Device (RCD), 1+N, rated current 25A, rated residual operating current IΔn 0,03A,
rated voltage 230 VAC, A-Type
Characteristic | Value |
---|---|
Article Nr | 752528098 |
PU | 1 |
EAN | 4008224656122 |
Connectable conductor cross section solid-core | 1,00 – 25,00 mm² |
Connectable conductor cross section multi-wired | 1,00 – 25,00 mm² |
Rated fault current | 0,03 A |
Rated insulation voltage Ui | 440 V |
Rated voltage | 230 V |
Rated impulse withstand voltage Uimp | 4,00 kV |
Rated current | 25,00 A |
Width in number of modular spacings | 2 |
Built-in depth | 68,0 mm |
Explosion-proof | no |
Leakage current type | A |
Frequency | 50/60 Hz |
Short-circuit breaking capacity (Icw) | 10,000 kA |
Short-time delayed tripping | no |
With interlocking device | no |
Mounting method | DIN rail |
Number of poles | 2 |
Surge current capacity | 0,400 kA |
Ambient temperature during operating | -25 – 55 °C |
Pollution degree | 2 |
Additional equipment possible | yes |
Netzstecker - Typbezeichnung | ohne |